How To Use Fluke I400 Current Clamp

Didactics Sail

i400

AC Current Clamp

Introduction

The Model i400 (futurity chosen "the Current Clench") is an ac electric current clamp that outputs 1 mA/A via safe-shrouded banana plugs; it is designed to extend the measuring adequacy of an air-conditioning current meter to 400 A.

Safety Information

XW Read First: Safe Information

To ensure safe operation and service of the Current Clamp, follow these instructions:

Read the operating instructions before use and follow all prophylactic instructions.

Employ the Current Clench only as specified in the operating instructions, otherwise the clamp's safety features may not protect y'all.

Attach to local and national safe codes. Private protective equipment must be used to preclude shock and arc smash injury where hazardous live conductors are exposed.

Do non hold the Current Clamp anywhere beyond the tactile barrier, see Figure 1.

Before each use, inspect the Current Clamp. Await for cracks or missing portions of the clamp housing or output cable insulation. Also look for loose or weakened components. Pay item attention to the insulation surrounding the jaws.

Never use the clamp on a circuit with voltages higher than 1000 Five True cat 3 or 600 V CAT Four.

True cat III equipment is designed to protect

against transients in equipment in stock-still­equipment installations, such every bit distribution panels, feeders and short branch circuits, and lighting systems in large buildings.

CAT IV equipment is designed to protect

against transients from the primary supply level, such equally an electricity meter or an overhead or hush-hush utility service.

Employ extreme caution when working around bare conductors or bus bars. Contact with the conductor could consequence in electric shock.

Use caution when working with voltages above sixty V dc or 30 V ac. Such voltages pose a shock hazard.

Symbols

Awarding around and removal from chancy alive

,

conductors is permitted.

T Product is protected by double insulation. W Take chances of Danger. Important information. See Educational activity Canvass. X Hazardous voltage.

Conforms to relevant Canadian Standards Clan

)

directives.

P Conforms to relevant European Wedlock directives.

PN 2282667 December 2004

© 2004 Fluke Corporation, All rights reserved. Printed in U.S.A. All product names are trademarks of their corresponding companies.

®

Electrical Specifications

Reference Conditions: 23 ± 5 ° C, twenty to 75 % RH; conductor centered in jaw opening; no dc component; no adjacent usher

Measurement Range: 1 A to 400 A air conditioning rms Output: i mA/A Accurateness: 2 % + 0.06 A, 45 Hz to 400 Hz Typical Bandwidth: v Hz to 20 kHz Working Voltage: 1000 5 ac rms, in compliance with

EN61010 Common Mode Voltage: grand V air conditioning rms from earth ground, in

compliance with EN61010

Load Impedance: < ten Maximum Not-subversive Current: one thousand A Duty Bike: 1 A to 400 A continuous Influence of Adjacent Conductor: < 7.five mA/A Influence of Conductor Position in Jaw Opening: ± 1.0 % of

reading + 0.05 A

Safety Specifications

Category Rating: True cat Three 1000 V and True cat Iv 600 V per EN61010-1, Pollution Caste 2 IEC 61010-02-032

EMC: EN 61326-1, FCC for emission and immunity

): Tested to Us and Canadian standards for compliance to

UL61010-one and CAN/CSA C22.two No. 101.ane:2004

P: IEC 61010-1 2

nd

Edition

Full general Specifications

Output Cable Length: 1.5 m Maximum Conductor Size: 32 mm Storage Temperature: -20 °C to 60 °C Operating Temperature: 0 °C to l °C Relative Humidity: 10 °C to thirty °C: 95 %

30 °C to forty °C: 75 % 40 °C to 50 °C: 45 % Temperature Coefficient: 0.01 X (specified accuracy)/ ° C

(< 18 °C or > 28 °C)

Altitude: Operating: 2000 m; Non-operating: 12000 m Dimensions: 150 x 70 ten 30 mm Weight: 114 g

Musical instrument Compatibility

The i400 is compatible with whatsoever Fluke Multimeter or whatsoever other current measurement device that has the following features:

20 mA ac or greater current range

Assistant inputs

Input accuracy of 2 % or better to take full advantage of

the accuracy of the Current Clamp.

Input impedance of < 10

Measurement Considerations

Discover the following guidelines for positioning the Electric current Clench jaws:

Center the conductor inside the Electric current Clamp jaw.

Make sure the clamp is perpendicular to the conductor.

For optimal reading, brand sure the usher is positioned

betwixt the alignment marks on the jaw of the Current Clamp.

Observe the following guidelines when making measurements:

Avoid taking measurements close to other electric current-conveying conductors.

The Current Clamp displays current readings at 1/1000 of the bodily current on the usher. For example, a 5 A input current will be transformed into a 5 mA output current.

Depression-Level Electric current Measurements

The Current Clamp is specified to measure currents of 1 A or greater. Measurement accuracy of currents less than 1 A is unspecified.

Operation

To utilize the i400, (refer to Figure 1):

Source: https://manualmachine.com/fluke/i400/15919081-instruction-manual/